5.1.3 Functional Specifications

The MVI69-HART module supports the HART Multi-drop implementation of the

protocol. Following are some general specifications for the module:
 Built accordance to the HART Bell 202 Frequency Shift Keying (FSK)

standard to superimpose digital signals at a low level on top of the 4 to 20 mA

o

Two independent HART master ports that are completely user-

configurable

o

Supports up to 15 devices per port

o

Point-to-point (slave address 0) or multi-drop (slave address 1 to 15)

modes supported

 Supports 99 universal and common practice commands per port to control

and monitor devices with integer, IEEE754 floating-point and packed ASCII

character string data blocks

 Burst mode can be used for faster update of data from a single slave
 Supports an auto polling feature that will automatically collect data from each

HART instrument on the channel and store the data in the module database

 Communication ports can be configured as a secondary Master (that is,

handheld configuration device)

Protocol Supported: HART protocol uses the Bell 202 standard frequency shift-
keying (FSK) digital signal to communicate at 1200 baud, superimposed at a low

level on the 4 to 20 mA analog measurement signal. The MVI69-HART module

supports version 5 of the HART protocol.
Supported Function Codes: HART Universal Commands Set supported are 00
to 03, 06 to 09, and 11 to 22. HART Common Practice Commands Set supported

are 33 to 83 and 105 to 110.
HART Network Communications: Supports two Master channels. Each

channel on the module is configured independently to emulate a HART Master.

Burst mode can be used for faster update of data from a slave device.
Command polling is also user-configurable, including disabled, continuous, on

change of data (write only), and dynamically user or automatic enabled.
Status: Error codes returned by the HART protocol available on an individual

command basis. In addition, a slave status list is maintained per active channel.