ProSoft Technology MVI69-HART User Manual

Page 30

Advertising
background image

Module Configuration

MVI69-HART ♦ CompactLogix Platform

User Manual

HART Multi-drop Master Communication Module

Page 30 of 169

ProSoft Technology, Inc.

March 29, 2012

Write Register Count
Range 0 to 4000
This parameter specifies the number of registers to transfer from the processor to

the module. Valid entry for this parameter is 0 to 4000.

Error/Status Offset
-1 or 0 to 3935
This parameter defines the database location where the module status data will

be stored. If set to -1, data not placed in database.

Failure Flag Count
0 through 65535
This parameter specifies the number of successive transfer errors that must

occur before halting communication on the application port(s). If the parameter is

set to 0, the application port(s) will continue to operate under all conditions. If the

value is set larger than 0 (1 to 65535), communications will cease if the specified

number of failures occur.

Initializing Output Data
Y

ES

or N

O

This parameter determines if the output data for the module should be initialized

with values from the processor. If the value is set to N

O

(0), the output data will

be initialized to 0. If the value is set to Y

ES

(1), the data will be initialized with

data from the processor. Setting this option to Y

ES

requires associated ladder

logic to pass the data from the processor to the module.

2.2.2 [HART PORT x]

The [HART PORT x] sections of the configuration file set the HART channel

communication parameters, define the protocol specifics and set the command

list parameters. The parameters are the same for all ports. The command list for

each HART channel is entered in a different section of the file.

Enabled
Y or N
This parameter enables or disables the specific HART channel. If the parameter

is set to "Y", the channel will be utilized. If set to "N", the channel will not be used.

Preambles
5 to 20
This parameter sets the number of preambles to be transmitted before each

message is sent from the channel. The value of 5 is normally utilized for the

parameter. It can be set to a value from 5 to 20.

Advertising