MVI69-HART ♦ CompactLogix Platform

Module Configuration

HART Multi-drop Master Communication Module

User Manual

ProSoft Technology, Inc.

Page 29 of 169

March 29, 2012

2.2

MVI69-HART Configuration File

The configuration file for MVI69-HART consists of the following sections.

Section

Description

[MODULE]

General module level parameters

[HART PORT 0]

HART Port (Channel) 0 configuration parameters

[HART PORT 0 COMMANDS]

HART command list for Port (Channel) 0

[HART PORT 1]

HART Port (Channel) 1 configuration parameters

[HART PORT 1 COMMANDS]

HART command list for Port (Channel) 1

2.2.1 [MODULE]

The [Module] section contains the data that applies to the whole module and

includes the backplane data transfer parameters.

Module Name
0 to 80

characters

This parameter assigns a name to the module that can be viewed using the

configuration/debug port. Use this parameter to identify the module and the

configuration file.

Block Transfer Size
60, 120 or 240
This read-only parameter specifies the number of words of user data transferred

in each block between the module and processor.

Read Register Start
0 to 3999
This parameter specifies the starting register address of a block of data registers

to transfer from the module to the processor. This will be used for data brought

into the processor from other nodes on the network.

Write Register Count
0 to 4000
This parameter specifies the number of registers to transfer from the processor to

the module.

Write Register Start
0 to 3999
This parameter specifies the starting register address of a module register block

where data transferred from the processor will be stored. This will be used for

data to be sent from the processor to other nodes on the network.