Reference

MVI69-HART ♦ CompactLogix Platform

User Manual

HART Multi-drop Master Communication Module

Page 88 of 169

ProSoft Technology, Inc.

March 29, 2012

This sequence will continue until interrupted by other write block numbers sent by

the controller or by a command request from a node on the HART network or

operator control through the module’s Configuration/Debug port.
The following example shows a typical backplane communication application.
If the backplane parameters are configured as follows:

Read Register Start: 0
Read Register Count: 480
Write Register Start: 480
Write Register Count: 480

The backplane communication would be configured as follows:

Database address 0 to 479 will be continuously transferred from the module to

the processor. Database address 480 to 959 will continuously be transferred

from the processor to the module.
The Block Transfer Size parameter basically configures how the Read Data and

Write Data areas are broken down into data blocks (60, 120, or 240).