7100FP EPA Woodburning Fireplace

R

B. Clearances

Figure 11.1 Clearances to Combustible Materials

Fire Risk
• Comply with all minimum clearances to combustibles as specified.
• Framing or finishing material used on the front of, or in front of, the

appliance closer than the minimums listed, must be constructed entirely
of non-combustible materials (i.e., steel studs, concrete board, etc.).

Failure to comply may cause fire.

WARNING

2 in. (51 mm) min.

Attic

Insulation

Shield

Ceiling Firestop

(ceiling)

(roof)

(attic)

(ceiling)

Ceiling Firestop

Offset/Return with

hanger straps

Storm Collar

Roof Flashing

2 in. (51 mm) min.

2 in. min.

(51 mm)

Must have 2 in. (51 mm)

minimum clearance

to header

2 in. (51 mm) min.

2 in. (51 mm) min.

2 in. (51 mm) min.

2 in. (51 mm) min.

1 in. (25mm) to side of appliance

(except at nailing flanges where it is 1/2 in. [13 mm])

1/2 in. (13 mm) to back

of appliance

0 in.

to floor

0 in. to level

of standoffs