Complete the enclosure, 7100fp epa woodburning fireplace, Chimney termination requirements – Hearth and Home Technologies EPA Certified Woodburning Fireplace 7100FP-GD-B User Manual

Page 26

Advertising
background image

Page 26

433-1390G

September 1, 2008

R

7100FP EPA Woodburning Fireplace

A Gas

Termination

Wood or Fuel Oil Termination

B 6

in.

(152 mm) min.

20 in.

(508 mm) min.

Gas, Wood or Fuel

Oil Termination

8 ft

(2.44 m)

(min. for B-Vent)

20 in.

(508 mm)

(min. for direct vent)

to

Perpendicular

Wall

18 in.

(457 mm)

A

Gas

Termination

B

Termination Caps Staggered Height

Figure 26.2 Multiple Chimneys

6

Complete the Enclosure

A. Chimney Termination (2-10-03 Rule)

Chimney Termination Requirements

(See Figures 26.1 and 26.2)

• Must have a cap approved and listed for this fireplace system
• Must not be located where it will become plugged by snow or other material
• Must terminate at least 3 ft (914 mm) above the roof and at least 2 ft (610 mm) above any portion of the roof within 10 ft

(3.05 m)

• Must be located away from trees or other structures

3 ft. (91cm)

Minimum

Less than 10 ft. (305cm)

2 ft. (61cm)

3 ft. (91cm)

Minimum

10 ft. (305cm) To Nearest Roofline

2 ft. (61cm)

Pitched Roof

Flat Roof

10 ft. (305cm) or more

3 ft. (91cm) Minimum

Less than 10 ft. (305cm)

2 ft. (61cm)Minimum

3 ft. (91cm) Minimum

Wall or Parapet

Figure 26.1 Termination Requirements