Warning, 7100fp epa woodburning fireplace, D. install the termination cap – Hearth and Home Technologies EPA Certified Woodburning Fireplace 7100FP-GD-B User Manual

Page 29: C. chase top

Advertising
background image

September 1, 2008

433-1390G

Page 29

7100FP EPA Woodburning Fireplace

R

Termination Cap

Storm Collar

Slope Downward

Turn-down

Drip Edge

Chase
(Chimney)

2 in. (51 mm) Collar
on Chase Top

Caulk

.018 (26 ga) min.
Galvanized
Chase Top

Figure 29.1 Chase Top Construction

2 in. (51 mm) min. collar

6 in. (152mm) min.

2 in. (51 mm) min.

Storm Collar

Flashing Collar

Minimum 1-1/2 in. (38 mm) overlap of cap over pipe

Figure 29.3 Installing a TR344 Round Termination Cap

Note: To protect against the effect of corrosion on those
parts exposed to the weather, the termination cap can be
painted with a rust-resistant paint.

Fire Risk
• The minimum overlap of cap to pipe

MUST be met or chimney may separate
from cap.

Separation allows sparks, heat and embers
to escape.

WARNING

D. Install the Termination Cap

For installations utilizing a Round Telescoping Termination

Cap, the uppermost chimney section must be below the
top of the chase top, but not more than 14-1/2 in. (368 mm)
below the top of the chase top. Minimum overlap of
chimney and termination cap must be 1-1/2 in. (38 mm).
See Figure 30.1 on page 30.

Install the chimney sections up through the chase

enclosure. When using a Round Termination Cap, the
uppermost top section of pipe must extend 6 in. (152 mm)
above the top of the flashing collar to allow installation of
the storm collar and termination cap. See Figure 29.3.

C. Chase Top

A metal chase top is required to seal the top of the chase
around the chimney pipe. The top should include a turn-
down and drip edge to prevent water from seeping into the
chase. Provide a 1/8 in. (3 mm) gap around the flue pipe
and slope the top downward away from the penetration. See
Figure 29.1.

• All seams must be caulked to prevent leaks.

A chase installation must use a chase top. Chase tops are
available from your Quadra-Fire dealer or may be field
constructed.

• Attach the chase top to the top of the chase.

Fire Risk
• Never install a single wall slip section or

smoke-pipe in a chase structure.

The higher temperature of this single wall
pipe may radiate sufficient heat to combus-
tible chase materials to cause a fire.

WARNING

Figure 29.2

Framing to top of chase must be constructed to support
service persons, snow load, etc. Maintain 2 in. (51 mm)
clearance to combustibles. Top of framing should be
sheeted with plywood particle board. See Figure 29.2.

• Chase Top Framing

Exterior sheeting

Chase top framing