Installation of fireplace, Caution – Hearth and Home Technologies EPA Certified Woodburning Fireplace 7100FP-GD-B User Manual

Page 15

Advertising
background image

September 1, 2008

433-1390G

Page 15

7100FP EPA Woodburning Fireplace

R

A. Install the Outside Air Kit

This fireplace will operate correctly only if adequate ventila-
tion is provided to allow proper draft to the fireplace system.
See Section 2.

Using an outside air kit must be used for combustion to mini-
mize the effects of negative pressure within the structure.
We recommend you utilize the shortest duct run to optimize
the performance of the outside air kit. The outside air kit inlet
should be positioned in a manner that will not allow snow,
leaves, etc. to block the inlet. In some installations the air
duct may need to be run vertically. In such an installation, a
3 ft (914 mm) height difference must be maintained from the
top of the uppermost chimney section to the outside com-
bustion air inlet. See Figure 16.1 on page 16.

See Figure 16.2 on page 16 for proper placement of outside
air inlet.

The outside air kit is installed on the right hand side of the
fireplace. See Figure 15.1 for handle location/operation.

4

Installation of Fireplace

Figure 15.1

Outside Air Installation

Termination

Caps supplied

with fireplace

6 in. (152 mm) rigid or flex pipe

(not provided)

Outside Air

intake

Auxiliary

Convection

Air

Open/Close

Knob for

outside air

OUTSIDE AIR

OPEN

CLOSED

1. Cut a 6 in. (152 mm) hole in outside wall to accommodate

air piping. The outside air is located on top, auxiliary
convection air intake is located on the bottom. See Figure
15.1.

2. Use 6 in. (152 mm) metal flex or rigid piping (not supplied)

to directly connect outside air to fireplace intake. Insulate
the pipe to prevent frost condensation.

3. Use the supplied termination caps.

4. Seal between the wall and the pipe with silicone to prevent

moisture penetration and air leaks.

5. Seal between the termination cap and the house with

silicone to prevent air infiltration.

NOTE: A control knob allows you control of the outside air

inlet. Use of outside air for combustion is required to
conserve heated air within the structure and to provide
make up air to keep the fireplace venting properly.

IMPORTANT!

TURN CLOCKWISE TO “OPEN” POSITION.

OUTSIDE AIR KNOB MUST BE IN THE “OPEN” POSI-
TION TO OPERATE FIREPLACE PROPERLY.

MAY BE CLOSED WHEN NOT IN USE TO PREVENT
COLD AIR INFILTRATION.

CAUTION

Sharp Edges

• Wear protective gloves

and safety glasses during
installation.

Advertising