Finishing, Warning – Hearth and Home Technologies EPA Certified Woodburning Fireplace 7100FP-GD-B User Manual

Page 38

Advertising
background image

Page 38

433-1390G

September 1, 2008

R

7100FP EPA Woodburning Fireplace

8

Finishing

A. Hearth Extension

A hearth extension must be installed with all fireplaces to
protect the combustible floor in front of the fireplace from
both radiant heat and sparks. See Figures 38.1 below, and
Figures 39.1 and 39.2 on page 39.

2 in. (51 mm)
required

High temperature
(300°F min.) continuous,
non-combustible sealant

Tile, stone or other
non-combustible material

Floor constructed of wood or
other combustible material

HX3 or HX4
Hearth Ext
or equivalent
insulation
(see Table below)

Fireplace

Protective
Metal Hearth
Strip

Figure 38.1 Hearth Extension Construction

Table 38.2

Hearth Extension Insulation Alternatives,

Minimum R Value = 2.06

Material

k per inch

thick

R per inch

thick

Minimum

thickness

required

Hearth & Home HX3, HX4

0.49

2.06

1 in.

USG Micore 300™

0.49

2.18

1 in.

USG Durock™ Cement Board

1.92

0.52

2-1/4 in.

Cement Mortor

5.0

0.20

5-7/8 in.

Common Brick

5.0

0.20

5-7/8 in.

Ceramic Tile

12.50

0.08

14-5/8 in.

Armstrong™ Privacy
Guard Plus

0.46

2.18

1/2 in.

Marble

14.3-20.0

0.07-0.05 16-5/8 in. - 23-3/8 in.

B. Calculating Alternate Floor Protection

Material

Thermal Conductivity: k value

The k value indicates the amount of heat (in BTU’s) that will flow
in 1 hour through 1 square foot of a uniform material 1 inch thick
for each degree (F) of temperature difference from one side of
the material to the other. The LOWER the k factor means less
heat is being conducted through the non-combustible material
to the combustible material beneath it. The k value of a mate-
rial must be equal or smaller then the required k value to be
acceptable.
(BTU)

(inch)

(foot

2

(hour) (

o

F)

Thermal Resistance: R value

The R value is a measure of a material’s resistance to
heat transfer. R value is convenient when more than one
material is used since you can add the R values together,
whereas you can not do this for k value. The HIGHER the R

factor means less heat is being conducted through the non-
combustible material to the combustible material beneath it.
The R value of a material must be equal or larger then the
required R value to be acceptable.

Converting k to R:

Divide 1 by k and multiply the results times the thickness in inch-
es of the material.

R = 1/k x inches of thickness

Converting R to k:

Divide the inches of thickness by R.

k = inches of thickness/R

Calculations:

Example: Floor protection requires k value of 0.84 and 3/4 inch
thick.

Alternative material has a k value of 0.6 and is 3/4 inch thick.

Divide 0.6 by .75 = k value of 0.80. This k value is smaller than
0.84 and therefore is acceptable.

Fire Risk
• Maintain

clearances.

• Use only non-combustible material below

standoffs, material such as cement board
is acceptable.

WARNING

• Framing or finishing material used on the front

of, or in front of, the appliance closer than the
minimums listed, must be constructed entirely of
noncombustible materials (i.e., steel studs, concrete
board, etc.).

Advertising