Warning, 7100fp epa woodburning fireplace – Hearth and Home Technologies EPA Certified Woodburning Fireplace 7100FP-GD-B User Manual

Page 23

Advertising
background image

September 1, 2008

433-1390G

Page 23

7100FP EPA Woodburning Fireplace

R

D. Assemble the Chimney Sections

Attach either a straight chimney section or an offset to the
top of the fireplace (depending on your installation require-
ment). Chimney sections are locked together by pushing
downward until the top section meets the stop bead on the
lower section.

The inner flue is placed to the inside of the flue section below
it. The outer casing is placed outside the outer casing of the
chimney section below it. See Figure 23.1.

If you are using a different approved venting system, follow
the instructions that were supplied with that system.

Note: Inner flue and outer liner sections cannot be
disassembled once locked together. Plan ahead to ensure
the proper installation height is achieved with the selected
chimney components.

Figure 23.1 Assembling Chimney Sections

Fire Risk

Do NOT install substitute or damaged
chimney components.
• MUST use chimney system described in

this manual.

• NO OTHER chimney components may

be used.

Substitute or damaged chimney components
may impair safe operation.

WARNING

E. Assembling Chimney Sections for the SL-

300 Series

NOTE: Chimney Air Kit, Part CAK4A is REQUIRED
when using the SL-300 Pipe Series. Detailed instruc-
tions are supplied with the kit.

If using the Dura-Plus System (must be 8 in. (203
mm) in diameter), the starter ring that came with the
fireplace must be removed and replaced with the
Dura-Plus Base Plate. The CAK4A is not required
with a Dura-Plus System.

Attach

Flue First

CAK4A

Secure with Screws

Provided

Push Together

Secure to Top

Installing CAK4A and Flex Pipe

NOTE: FOLLOW DETAILED INSTRUCTIONS THAT COME

WITH THE CAK4A.

1. Install the chimney pipe first.

2. Hand bend the tabs in position before placing on the

fireplace.

3. Place the box on top of the fireplace around the chimney

pipe, push both pieces together and secure with screws
provided.

4. Use the pre-punched holes in the tabs as guides and drill

holes through the fireplace top.

5. Secure the CAK4A in place.

6. Seal around the kit at the flue and at the top of the can

with caulk.

NOTES:

1. The outside air termination cap must be a minimum of 6 ft

(1829 mm) above the ground and kept free of debris and
must be at least 3 ft (914 mm) below the chimney top, if
installed in the chase zone.

2. Seal around the cap and flex with caulk to stop air from

getting in to the chase (See Figure 24.1 on page 24).

Figure 23.2 Installing the CAK4A

Advertising