Power-Up Procedure

1. Fill out the Polling Loop Current Draw and Auxiliary Device Current Draw

Worksheets shown below. Make sure that the currents drawn from these
outputs do not exceed their respective ratings.

CAUTION: Failure to observe the polling loop current rating will cause a
polling loop malfunction. Failure to observe the auxiliary output current rating
will result in a battery which does not charge properly, or possibly a tripped
circuit breaker.

2. Wire the 1361 transformer (1361CN in Canada) to terminals 1 & 2 on the

control panel (before connecting the battery), as shown in the SUMMARY OF
CONNECTIONS diagram. Do not plug in at this time.

3. Connect all polling loop and auxiliary devices, such as keypads, PIRs, etc.

4. Plug the transformer into a 24-hour, uninterrupted AC outlet. After a few

seconds, the green READY LED on the keypad(s) should light and the
keypad(s) should display DISARMED READY TO ARM (Alpha keypads), or
READY (Fixed-word keypads).

5. Connect the battery to the battery tabs on the control board using the battery

cables supplied (use Red for + to +, Black for Ð to Ð). See the SUMMARY OF
CONNECTIONS diagram.

POLLING LOOP CURRENT DRAW WORKSHEET

RPM DEVICE

C U R R E N T

# UNITS

TOTAL CURRENT

998MX PIR

1mA

4191SN Contact

1mA

4194 Contact

1 mA

4192SD Photo Smoke

0.4 mA

4192SDT Smoke w/Heat

0.4 mA

4192CP Ionization Detector

0.4 mA

4275 Dual Element PIR

1 mA

4278 Quad Element PIR

1 mA

4190WH 2-Zone RPM

1 mA (LOW)
2 mA (HIGH)

4208 8-Zone RPM

16 mA

4278EX-SN PIR

1mA

4939SN Contact

1mA

4959SN Contact

1mA

TOTAL CURRENT *

* If the total current draw exceeds 64 mA, a 4197 Loop Extender module must be used.

AUXILIARY DEVICE CURRENT DRAW WORKSHEET

D E V I C E

C U R R E N T

# UNITS

TOTAL CURRENT

6128 Keypad

30mA

6137 Keypad

85mA

6139 Keypad

100mA

6139AV Keypad

200mA

675 Ground Start Module

50 mA

Built-in Polling Loop

(total poll loop worksht)

4281 RF Receiver

35mA

5881 RF Receiver

60mA

4197 Poll Loop Extender

80 mA

4204 Relay Module

15mA standby
40mA

per active relay

VIM

Voice Interface Module.

80mA

*
*

TOTAL CURRENT (750mA max)

*

If using hard-wire devices such as PIRs, refer to the specifications for that particular unit's current draw.

Only applies if powered from Control's auxiliary power.