Using a trigger to activate a non-ademco aav unit – Guardian Technologies Ademco VISTA-40 User Manual

Page 30

Advertising
background image

Р 30 Р

Remote Keypad Sounder

Operation & Wiring

An optional Amseco PAL 328N can be used for installations where it is desired to
remote the sounds produced by the keypad's built-in piezo sounder for one
partition. The panel will remote all sounds (i.e. alarm, trouble, chime, entry/exit,
etc.) produced by the keypad's built-in sounder except for the short clicks
associated with keypad key depression. One application of this feature might be
to produce chime sounds in a location which is distant from the panel's keypads.
This can also be accomplished using relay outputs (see Output Relay section).

If used, program field 1*46 must be set to "2" to enable the remote keypad
sounder option, and the Amseco piezo must be connected between the panel's
auxiliary power and the J7 connector trigger output as shown below.

In addition, field *15 must be used to select the partition whose keypad sounds
are to trigger the sounder. Zone 7 must be assigned to be a keyswitch zone
(even if keyswitch is not used).

1

2 3

4 5

6

7

8

9

GRAY

YELLOW

WHITE

RED

GREEN

BROWN

BLUE

BLACK

GROUND

OUT 1

GROUND

OUT 2

GROUND

OUT 3

GROUND

OUT 4

J7 CONNECTOR

IF USED.
1. OUT 1 IS NO LONGER

USABLE FOR OPEN/CLOSE
OR GROUND START (SEE
FIELD 1*46).

2. OUT 2, 3, 4 CAN STILL BE

USED TO PROVIDE ALARM
STATUS INDICATIONS OR
TO OPERATE A KEYSWITCH
(SEE FIELD *15).

N/U

4142TR CABLE

BLACK

AMSECO PAL-328N
PIEZO SOUNDER

+

RED

TO AUX POWER +
TERMINAL 6
(10mA CURRENT DRAW)

REMOTE KEYPAD SOUNDING CONNECTIONS

Using A Trigger To

Activate Another

ManufacturerÕs AAV

Unit (if necessary)

If using an Audio Alarm Verification module from another manufacturer, and a
voltage trigger will be used to activate the module, make connections as shown
below. In addition, set program field 1*46 to option 3, and program zone 5 for
response type 10; also, program field 1*60 for Т1У.

Note:

If field 1*60 is set for Т1У, zone 5 cannot be used as a protection zone,

and the EOLR must be removed. Refer to the

2-WAY VOICE KEYPADS &

AUDIO ALARM VERIFICATION

section later in this manual for additional

information.

1

2

3 4

5 6

7

8

9

GRAY

YELLOW

WHITE

RED

GREEN

BROWN

BLUE

BLACK

GROUND

OUT 1

GROUND

OUT 2

GROUND

OUT 3

GROUND

OUT 4

J7 CONNECTOR

N/U

4142TR CABLE

TO AUDIO ALARM
VERIFICATION MODULE
(AAV) FALLING EDGE
TRIGGER INPUT
ON THE AAV UNIT

DIODE INCLUDED
WITH EOLR
PACKAGE

USING A TRIGGER TO ACTIVATE A NON-ADEMCO AAV UNIT