Section 5. ZONE CONFIGURATIONS

BASIC 9 HARD-WIRED ZONES

General Information

Zones 1-9 are reserved for traditional hard-wired devices. The following table summarizes
zone usage.

Zone 1

EOLR supervised or closed circuit unsupervised devices. Also

supports up to sixteen (16) 2-wire smoke detectors.

Zones 2, 3, 4, 6

EOLR supervised or closed circuit unsupervised devices. Also
supports 4-wire smoke detectors.

Zone 5

EOLR supervised or closed circuit unsupervised devices. Also

supports 4-wire smoke detectors.

Zone 7

EOLR supervised or closed circuit unsupervised devices. Also

supports 4-wire smoke detectors. Alternatively, can be used to
support remote keyswitch. If used for keyswitch, it cannot be used
as protection zone.

Zone 8

EOLR supervised or closed circuit unsupervised devices. Also

supports 4-wire smoke detectors. Zone 8 also supports latching
glass break detectors.

Zone 9

Unsupervised devices only. Programmable for fast response
(10mS). Can monitor fast acting glass break detectors or vibration
sensors if set for fast response.

Programmable Response Time For Zone 9:
Zone response time for zone 9 can be set to either 350mS (normal) or 10mS (fast) via
program field *14.

Hard-wired Zone 1

UL NOTE: EOLRs are required for UL installations.

Applications

Can be used for EOLR supervised or closed circuit
unsupervised devices. It is the only zone that supports up to
sixteen (16) 2-wire smoke detectors.

Zone Response Type

Any, except type 23 (no alarm)

Max. Zone Resistance 100 ohms, excluding EOLR

Unsupervised Usage

¥ Cut red PCB jumper.

¥ Only closed circuit devices can be used.

EOLR Supervised

¥ Leave red PCB jumper intact.

¥ Supports both open circuit and closed circuit devices.
¥ Connect open circuit device in parallel across the loop. The

2,000 ohm EOLR must be connected across the loop wires
at the last device.

¥ Connect closed circuit device in series with the loop.

EOLR Fire Zone:

¥ Leave red PCB jumper intact.

¥ Assign zone type 09 (fire)
¥ Supports up to sixteen (16) 2-wire smoke detectors.
¥ Second CODE + OFF sequence momentarily interrupts

power to reset the smoke detectors.

¥ See table that follows for compatible detectors.