Guardian Technologies Ademco VISTA-40 User Manual

Page 66

Advertising
background image

Р 66 Р

The following is a list of choices for (ZT):

CHOICES FOR ZONE
T Y P E S :
00 = No Response (Not Used)
01 = Entry/Exit #1
02 = Entry/exit #2
03 = Perimeter
04 = Interior Follower
05 = Trouble Day/Alarm Night
06 = 24 Hr Silent
07 = 24 Hr Audible
08 = 24 Hr Aux
09 = Fire Alarm or Trouble
10 = Interior w/Delay
23 = No alarm response

CHOICES FOR SYSTEM OPERATION:
20 = Arming-Stay (5800 RF)
21 = Arming-Away (5800 RF)
22 = Disarming (Code+Off) (5800 RF)
31 = End of Exit Time
32 = Start of Entry Time
33 = Any Burglary Alarm
34 = Code + # + 71 Key Entry
35 = Code + # + 72 Key Entry
36 = At Bell Timeout **
37 = 2 Times Bell Timeout**
38 = Chime
39 = Any Fire Alarm
40 = Bypassing
41 = AC Power Fail
42 = System Battery Low
43 = Communication failure
44 = RF low battery
45 = Polling loop failure
47 = Keypad failure
51 = RF receiver failure
52 = kissoff
54 = fire zone reset
55 = disarm + 1 minute
56 = XX minutes (enter XX in field 1

*

74; stop

condition only)

57 = YY seconds (enter YY in field 1

*

75; stop

Ê condition only)

58 = Duress
60 = Select only if a non-Ademco AAV unit is

being used; also select for Start and Stop
if a 4204 relay module is being used.

64 = VIM Fail
65 = VIM Active
66 = VIM Inactive

** Or at Disarming, whichever occurs earlier

S T O P
The "STOP" programming determines when and under what conditions the relay
will deactivate. The following items can be programmed: Restore Zone List, Zone
type/System Operation, and Partition.

1) RESTORE ZONE LIST (ZL)....If a "RESTORE ZONE LIST" is used, the

relay action will deactivate when all the zones in that list restore from a
previous fault or alarm condition. This will occur regardless of what is
programmed to start the relay, therefore, a "RESTORE ZONE LIST" would
normally only be used when a "ZONE LIST" is used to start the relay.

2) ZONE TYPE/SYSTEM OPERATION (ZT)....Instead of using a

"RESTORE ZONE LIST" , a specific zone response type or action can be
selected to deactivate the relay. If a specific zone response type is chosen,
any zone of that type that restores from a previous alarm, trouble, or fault
condition will cause the relay to deactivate. If a "SYSTEM OPERATION" is
chosen, that operation will cause the relay to deactivate.

Relay Programming

M e n u s

From #93 Menu Mode, select Relay Programming Menu.

Press [*] to advance to next screen. Press # to backup to previous screen.

ENTER RELAY NO.
(00=QUIT) 01

Enter the relay (output device) identification number
1 - 8 . This is a reference number only, for
identification purposes. The actual module address
and relay number on the module are programmed in
the last two prompts.