Guardian Technologies Ademco VISTA-40 User Manual

Page 44

Advertising
background image

Р 44 Р

Type 05

Trouble by Day/Alarm

by Night.

This zone type will give an instant alarm if faulted when armed in the Away, Stay,
Instant or Maximum (night) modes. During the disarmed state (day), the system
will provide a latched trouble sounding from the keypad (and a central station
report, if desired). This zone type is usually assigned to a zone which contains a
foil-protected door or window (such as in a store), or to a zone covering a
"sensitive" area such as a stock room, drug supply room, etc. This zone type can
also be used on a sensor or contact in an area where immediate notification of an
entry is desired.

Type 06

24-hour Silent Alarm.

This zone type sends a report to the Central Station but provides no keypad
display or sounding. This zone type is usually assigned to a zone containing an
Emergency button.

Type 07

24-hour Audible Alarm.

This zone type sends a report to the Central Station, and provides an alarm sound
at the keypad, and an audible external alarm. This zone type is usually assigned to
a zone that has an Emergency button.

Type 08

24-hour Auxiliary

Alarm.

This zone type sends a report to Central Station and provides an alarm sound at
the keypad. (No bell output is provided). This zone type is usually
assigned to a zone containing a button for use in personal emergencies, or to a
zone containing monitoring devices such as water sensors, temperature sensors,
etc.

Type 09

Supervised Fire. (No

Verification)

This zone type provides a fire alarm on short circuit and a trouble condition on
open circuit. The bell output will pulse when this zone type is faulted. This zone
type is always active and cannot be bypassed. This zone type can be
assigned to any hard-wired zone except zone 9, any polling loop
zone, and certain wireless zones.

Type 1 0

Interior w/Delay.

This zone type gives entry delay (using the programmed entry delay 1 time), if
tripped when the panel is armed in the Away mode. This zone type is also active
during maximum mode, but no delay is provided (alarms occur immediately if zone
is tripped). This zone type is bypassed when the panel is armed in
the Stay or Instant modes.
Delay begins whenever sensors in this zone are
violated, regardless of whether or not an entry/exit delay zone was tripped first.

Type 20

Arm-Stay*

This is a special-purpose zone type used with 5800 series wireless pushbutton
units which will result in arming the system in the STAY mode when the zone is
activated.

Type 21

Arm-Away*

This is a special-purpose zone type used with 5800 series wireless pushbutton
units which will result in arming the system in the AWAY mode when the zone is
activated.

Type 22

Disarm*

This is a special purpose zone type used with 5800 series wireless pushbutton or
contact closure or opening, and which will result in disarming the system when
the zone is activated.

Type 23

No Alarm Response

This zone type can be used on a zone when an output relay action is desired, but
with no accompanying alarm (ex. lobby door access).

* These zone types are not for use by 5700 series devices.

NOTE FOR PANIC KEYS
Keypad panic zones share the same zone response type for both partitions, but
panics may be individually enabled for each partition.

IMPORTANT! FAULT ANNUNCIATION
Phone module, RF, VIM and polling loop faults (zones 87, 88-91, 93 & 97) will
report as trouble conditions only, and as such, should be assigned either zone
type 00 if no annunciation is desired, or zone type 05 if annunciation as trouble
condition is desired. See FAULT ANNUNCIATION notes in POLLING LOOP and
WIRELESS EXPANSION sections for more information.

Advertising
This manual is related to the following products: