Section 3. POWERING THE SYSTEM

Primary Power

Power to the Control panel is supplied by model No. 1361* Plug-in Transformer
which is rated at 16.5VAC, 40VA. Caution must be taken when wiring this
transformer to the panel to guard against blowing the fuse inside the transformer
(non-replaceable).

* NOTE: Use 1361CN Transformer in Canadian installations.

Back-Up Power

In the event of an AC power loss, the Control panel is supported by a back-up,
rechargeable gel cell battery. Ademco 467 (12V, 4AH), YUASA NP4-12 (12V,
4AH) and NP7-12 (12V, 7AH) batteries are recommended. Do not use Gates
batteries.

The standby battery is automatically tested every 24 hours, beginning 24 hours
after exiting programming mode. In addition, entry into the test mode will cause a
battery test to be initiated.

Battery Standby Table

AUX. STANDBY CURRENT DRAW

AMP-HRS.

200mA 400mA 600mA 750mA

4.0

6 hrs.

4 hrs.

3 hrs.

2.5 hrs.

6.0-7.0

11 hrs. 7 hrs.

5.5 hrs. 4 hrs.

N O T E : These figures are
approximate, and may vary
depending upon the age, quality,
and capacity of the battery at
the time of the AC loss.

Earth Ground

Connections

In order for the lightning transient protective devices in this product to be
effective, the designated earth ground terminal must be terminated in a good
earth ground. The following are examples of good earth grounds available at most
installations:

Metal Cold Water Pipe: Use a non-corrosive metal strap (copper is
recommended) firmly secured to the pipe to which the ground lead is electrically
connected and secured.
AC Power Outlet Ground: Available from 3-prong, 120VAC, power outlets
only. To test the integrity of the ground terminal, use a three-wire circuit tester
with neon lamp indicators, such as the UL-Listed Ideal Model 61-035, or
equivalent, available at most electrical supply stores.

NO CONNECTION

TRANSFORMER

16.5VAC, 40VA

ADEMCO No.1361

(IN CANADA

USE No. 1361CN)

or 4300 IF

X-10 DEVICES
WILL BE USED

Connect to

24hr. 120VAC,

60 Hz Outlet

1

2

3

RED (+)

BLK (–)

Connect to

12VDC, 4AH

or 12VDC, 7AH

GEL CELL

BATTERY

CHARGING

VOLTAGE

13.7 VDC

Replace

every

3 years

NOTE:

WHEN POWERING UP

THE PANEL, PLUG THE

TRANSFORMER IN BEFORE

CONNECTING THE BATTERY.

BATTERY

TABS

PRIMARY POWER
Supplied by 1361*
Plug-in
Transformer which
is rated at
16.5VAC, 40VA.
Caution must be
taken when wiring
this transformer to
the panel to guard
against blowing the
fuse inside the
transformer (non-
replaceable).

AC POWER AND BATTERY CONNECTIONS