Attenuation test results, Attenuation detail, Attenuation graph – Microtest TSB-67 - 568A Annex E User Manual

Page 25: Attenuation-to-crosstalk ratio (acr)

Advertising
background image

Page 25

Attenuation Test Results

To display the

ATTENUATION

screen, press

View (F1)

from the

AUTOTEST RESULTS

screen,

then press the

¬

arrow key until the

ATTENUATION

screen is displayed.

At the upper left of the screen, the pair corresponding to the displayed result is shown. The
Attenuation, in decibels (dB), is shown centered and the frequency is shown to the right. The
PASS/FAIL bar across the screen compares the measured Attenuation value to the Attenuation
limit value. The Autotest name is displayed after

Spec:

at the lower left of the screen.

Press

Detail (F1)

to display the frequency sweep range and the test results for all pairs.

Press

Pair (F3)

to toggle through the Attenuation results for each pair combination.

Press the

Ï

or

Ð

arrow key to display the previous or next test results screen.

Press the

ESCAPE

key to return to the

AUTOTEST RESULTS

screen.

Note: For diagnostic purposes, you can run Attenuation continuously by pressing the Measure
Cable Performance key and selecting Attenuation.

Attenuation Detail

To display this screen, press

Detail (F1)

from the

ATTENUATION

screen. This screen displays the

frequency sweep range and the worst case Attenuation for each pair.

Press

Graph (F1)

to enter graphing mode.

Graph (F1)

is available when

Save Sweep Data: Attn

has been selected in the

SAVE AUTOTEST

screen or when viewing results immediately after

running the Autotest.

Press

Pair (F3)

to toggle through the available pair combinations.

Press the

ESCAPE

key to return to the Attenuation screen.

Attenuation Graph

To display this screen, press

Detail (F1)

from the

ATTENUATION

screen, then press

Graph (F1).

This screen displays the Attenuation graph for the indicated pair combination.

Press

Zoom (F1)

to magnify the area of the graph around the cursor. The Zoom key can select 1x,

2x, 5x or 10x magnification.

Press

Print (F2)

to print the Attenuation graph.

Press the

ESCAPE

key to return to the Attenuation Detail screen.

Attenuation-to-Crosstalk Ratio (ACR)

Attenuation-to-Crosstalk Ratio (ACR) is an indication of how much larger the received signal is
compared to the noise (NEXT) on the same pair. ACR reports the difference between NEXT and
Attenuation on the cable. Both Attenuation and NEXT are measured and the ACR value is
computed at each measured Attenuation frequency. The worst case ACR is reported for each pair
combination.