7. electrical service guide, 8. connecting input power – Miller Electric Welder User Manual

Page 21

Advertising
background image

OM-196 188 Page 15

3-7.

Electrical Service Guide

Three-Phase

Input Voltage

400

Input Amperes At Rated Output

31

Max Recommended Standard Fuse Or Circuit Breaker Rating In Amperes

45

Min Input Conductor Size In AWG/Kcmil

10

Max Recommended Input Conductor Length

In Feet (Meters)

264 (80)

Min Grounding Conductor Size In AWG/Kcmil

10

Reference: 1993 National Electrical Code (NEC).

S-0092J

3-8.

Connecting Input Power

ssb2.4* 1/94 – ST-801 718 / ST-801 946

Tools Needed:

5/16 in

Input Filter

Board

L1

=GND/PE

Y

Always connect
grounding conductor
first.

Y

Turn Off welding power source, and
check voltage on input capacitors ac-
cording to Section 5-3 before
proceeding.

Check input voltage available at site.

Remove left side panel.

1

Input And Grounding Conductors

See Section 3-7.
Install ring terminals of proper size onto input
conductors for connection to input filter
board terminals (see illustration).
2

Line Disconnect Device

Select type and size of overcurrent protec-
tion using Section 3-7. Connect input and
grounding conductors to a deenergized line
disconnect device.

Reinstall left side panel.

L1

2

L2

L3

1

L2

L3