OM-196 188 Page 32

5-9.

Diagnostic LED’s On Customer Interface Board PC14

LED

Status

Diagnosis

1

On

Indicates –15 volts dc RA supply is present on customer interface board PC14.

1

Off

Indicates –15 volts dc RA supply is not present on customer interface board PC14.

2

On

Indicates +15 volts dc RA supply is present on customer interface board PC14.

2

Off

Indicates +15 volts dc RA supply is not present on customer interface board PC14.

3

On

Input signal On from robot for no Emergency Stop.

3

Off

Input signal Off from robot for Emergency Stop.

4

On

Indicates +24 volts dc RD supply is present on customer interface board PC14.

4

Off

Indicates +24 volts dc RD supply is not present on customer interface board PC14.

5

On

Input signal On from robot for shielding gas.

Off

Input signal Off from robot for no shielding gas.

6

On

Input signal On from robot to energize contactor.

Off

Input signal Off from robot to not energize contactor.

7

On

Input signal On from robot for jog retract.

Off

Input signal Off from robot for no jog retract.

8

On

Input signal On from robot for jog advance.

8

Off

Input signal Off from robot for no jog advance.

9

On

Indicates automatic configuration Bit D is set.

9

Off

Indicates automatic configuration Bit D is not set.

10

On

Input signal On for RPS-C.

10

Off

Input signal Off for RPS-C.

11

On

Input signal On for RPS-B.

11

Off

Input signal Off for RPS-B.

12

On

Indicates remote program A selected.

Off

Indicates remote program A not selected.

13

On

Input signal On from peripheral for touch sensor.

Off

Input signal Off from peripheral for no touch sensor.

14

On

Indicates automatic configuration Bit B is set.

14

Off

Indicates automatic configuration Bit B is not set.

15

On

Indicates automatic configuration Bit A is set.

15

Off

Indicates automatic configuration Bit A is not set.

16

On

Indicates automatic configuration Bit C is set.

16

Off

Indicates automatic configuration Bit C is not set.

17

On

Input signal On from relay CR4 for wire stuck in weld joint.

17

Off

Input signal Off from relay CR4 for wire not stuck in weld joint.

18

On

Input signal On from relay CR6 for flow (shielding gas or coolant) present.

18

Off

Input signal Off from relay CR6 for flow (shielding gas or coolant) not present.

19

On

Input signal On from relay CR5 for arc detect.

19

Off

Input signal Off from relay CR5 for no arc detect.

20

On

Input signal On from relay CR2.

Off

Input signal Off from relay CR2.

On

Input signal On from relay CR1 for welding power source ready and no detected errors present.

21

Off

Input signal Off from relay CR1 for welding power source not ready, detected errors are present, or unit
is in Setup or Control mode.

22

On

Input signal On from peripheral for flow switch.

Off

Input signal Off from peripheral for no flow switch.