Current share sub-register, Current share sub-register –35, Table 5-12 – Xantrex Technology XTR 850 Watt User Manual

Page 157: Operation shutdown status register –35, Table 5-13, Operation shutdown protection status register –35

Advertising
background image

OPERation Status Register

975-0200-01-01

5-35

5

Current SHare Sub-Register

This register shows the state of the current share configuration, which can
either be set through the front panel Current Share Config menu, or
through the SCPI command.

The SCPI command (s) for these instructions are:

[[:]SOURce]:COMBine:CSHare[:MODE]

Table 5-12 OPERation SHUTdown Status Register

Bit

Bit Weight

Bit Name

Description

0

1

PROTection

Reflects the summary of the PROTection sub-
register.

1

2

INTerlock

The power supply is shut down by INTerlock signal.

2

4

Not Used

Not Used

3

8

External Shutdown

The power supply is shut down by External
Shutdown signal.

Table 5-13 OPERation SHUTdown PROTection Status Register

Bit

Bit Weight

Bit Name

Description

0

1

OVP

Over Voltage protection has tripped.

1

2

UVP

Under Voltage protection has tripped.

2

4

Not Used

Not Used

3

8

Not Used

Not Used

4

16

AC Off

AC failure protection has tripped.

5

32

OTP

Over Temperature protection has tripped.

6

64

Not Used

Not Used

7

128

Foldback

Foldback protection has tripped.

8

256

Fan

Fan failure protection has tripped.

Advertising