SENA ProBee-ZE10 User Manual

Page 45

Advertising
background image

45

ProBee-ZE10 User Guide Rev.1.5

0 (Low) and 1 (High) if the pins are configured as digital I/O lines. If the pins are configured as analog

inputs, the corresponding return values are shown as *.

AT+DIO?<CR> or AT+DIO<number>?<CR>

, where <number> is the specific IO number between ranges 0 ~ 12 to read

AT+DIO command can also be used to set the digital output lines.

AT+DIO=<value><CR> or AT+DIO<number>=<value><CR>

, where <number> is the specific IO number between ranges 0 ~ 12 to read, and the <values> is a

combination of 0 or 1, 0 = Low, 1 = High

The analog input values can be read using the AT+AI command. Return value is a combination of 16-bit

hexadecimal integer between 0~2EE0(0~1200mV) or D120-FFFF(-1200~-1mV) which unit value

corresponds to 0.1mv. To convert the hexadecimal value to the actual voltage, please use the formula

below. If the pins are configured as digital I/Os, the corresponding return values are shown as *.

AT+AI?<CR> or AT+AI<number>?<CR>

, where <number> is the specific IO number between ranges 0 ~ 3 to read

If the Value is between 0 ~ 2EE0, Voltage (mV) = Value * 0.1

If the Value is between D120 ~ FFFF, Voltage (mV) = (Value – 65536) * 0.1

Example)

AT+DIO?<CR>

10001**011100

 DIO 0, 4, 8, 9, 10 are ON. GPIO5, 6 are configured as

analog inputs

OK

AT+DIO0=0<CR>

OK

AT+DIO?<CR>

00001**011100

 DIO 4, 8, 9, 10 are ON. GPIO5, 6 are configured as analog

inputs

OK

AT+AIO?<CR>

****,****,192A,13E8

 AI 2, 3(GPIO5, 6) are used. The others are

configured as DIO.

OK

To get/set the I/O values of the remote devices, remote AT commands can be used as below.

Advertising