Af-60 lp™ micro drive programming guide, 0-31 custom readout min scale, 0-32 custom readout max scale – GE Industrial Solutions AF-60 LP Micro Drive User Manual

Page 13: 0-4* keypad

Advertising
background image

the motor is coasted

OR

the set-ups between which the shift happens are linked to each other (see par. 0-12, Linked Set-ups).

If changing between set-ups that are not linked, the change will not happen before motor is coasted.

NB!

The motor is only considered stopped when it is coasted.

[1 ]

*

Set-up 1

Set-up 1 is active.

[2]

Set-up 2

Set-up 2 is active.

[9]

Multi Set-up

Select the active set-up via digital input and/or bus, see par. 5-1* choice [23].

0-11 Edit Set-up

Option:

Function:

The Edit Set-up is for updating parameters in the frequency converter from either Keypad or bus. It can be identical

or different from the Active Set-up.

All set-ups can be edited during operation, independently of the active set-up.

[1 ]

*

Set-up 1

Update parameters in Set-up 1.

[2]

Set-up 2

Update parameters in Set-up 2.

[9]

Active Set-up

Update parameters in set-up selected as Active Set-up (see par. 0-10).

0-12 Link Set-ups

Option:

Function:

The link ensures synchronizing of the “not changeable during operation” parameter values enabling shift from one

set-up to another during operation.

If the set-ups are not linked, a change between them is not possible while the motor is running. Thus the set-up change

does not occur until the motor is coasted.

[0]

Not linked

Leaves parameters unchanged in both set-ups and cannot be changed while motor runs.

[1 ]

*

Linked

Copy parameters “not changeable during operation” parameter values into presently selected Edit Set-up.

NB!

This parameter cannot be changed while motor runs.

4.1.2. 0-31 Custom Readout Min Scale

0-31 Custom Readout Min Scale

Range:

Function:

0.00

*

[0.00 – 9999.00 ]

It is possible to create a customized readout related to the output frequency of the unit. The value entered in par. 0-31

will be shown at 0 Hz. The readout can be shown in the LCP display when in Status Mode or it can be read in par. 16-09

4.1.3. 0-32 Custom Readout Max Scale

0-32 Custom Readout Max Scale

Range:

Function:

100.0

*

[0.00 – 9999.00]

It is possible to create a customized readout related to the output frequency of the unit. The value entered in par. 0-32

will be shown at the frequency programmed in par. 4-14 Motor Speed High Limit. The readout can be shown in the LCP

display when in Status Mode or it can be read in par. 16-09

4.1.4. 0-4* Keypad

The frequency converter can operate in the following three modes: Hand, Off and Auto.

Hand: The frequency converter is locally operated and does not allow any remote control. By activating Hand a start signal is given.

OFF: The frequency converter stops with a normal stop ramp. When Off is chosen the frequency converter can only be started by pressing either Hand or Auto

on the Keypad.

AF-60 LP™ Micro Drive Programming Guide