6-15 Terminal 53 High Ref./Feedb. Value

Range:

Function:

The scaling value corresponding to the maximum reference feedback value set in parameters 6-11 and 6-13.

50.000

*

[-4999.000 - 4999.000]

Enter analog input scaling value.

6-16 Terminal 53 Filter Time Constant

Range:

Function:

A first-order digital low pass filter time constant for suppressing electrical noise in terminal 53. A high time constant

value improves dampening but also increases time delay through the filter.

0.01 s

*

[0.01 - 10.00 s]

Enter time constant.

6-19 Terminal 53 Mode

Option:

Function:

Select the input to be present on terminal 53.

Par. 6-19 MUST be set according to Micro switch 4 setting.

[0]

*

Voltage Mode

[1]

Current Mode

4.7.4. 6-2* Analog Input 2

Parameters for configuring scaling and limits for analog input 2, terminal 60.

6-22 Terminal 60 Low Current

Range:

Function:

This reference signal should correspond to minimum reference value set in par. 3-02.

0.14 mA

*

[0.00 - 19.90 mA]

Enter low current value.

The value must be set to min. 2 mA in order to activate the Live Zero Timeout function in par. 6-01.

6-23 Terminal 60 High Current

Range:

Function:

This reference signal should correspond to the high current value set in par. 6-25.

20.00 mA

*

[0.10 - 20.00 mA]

Enter high current value.

6-24 Terminal 60 Low Ref./Feedb. Value

Range:

Function:

The scaling value should correspond to the minimum reference feedback value set in par. 3-02.

0.000

*

[-4999 - 4999]

Enter analog input scaling value.

6-25 Terminal 60 High Ref./Feedb. Value

Range:

Function:

The scaling value should correspond to the maximum reference feedback value set in par. 3-03.

50.00

*

[-4999 - 4999]

Enter analog input scaling value.

AF-60 LP™ Micro Drive Programming Guide

38

4