Parameter group 14: special functions, Af-60 lp™ micro drive programming guide – GE Industrial Solutions AF-60 LP Micro Drive User Manual

Page 55

Advertising
background image

4.11. Parameter Group 14: Special Functions

4.11.1. 14-** Special Functions

Parameter group for configuring special frequency converter functions.

4.11.2. Carrier Frequency 14-0*

Parameters for configuring the carrier frequency.

14-01 Motor Noise (Carrier Frequency)

Option:

Function:

Select the carrier frequency in order to minimize e.g. acoustic noise and power loss or maximizing efficiency.

[0]

2 KHz

[1]

*

4 KHz

[2]

8 KHz

[4]

16 KHz

14-03 Overmodulation

Option:

Function:

This feature allows more accurate speed control near and over nominal speed (50/60 Hz). Another advantage with

overmodulation is the ability of staying at a constant speed even though mains is dropping.

[0]

Off

Disables the overmodulation function to avoid torque ripple on the motor shaft.

[1]

*

On

Connects the overmodulation function to obtain an output voltage up to 15% greater than mains voltage.

4.11.3. 14-1* Mains Monitoring

This parameter group supplies functions for handling imbalance on mains.

14-12 Functions at Mains Imbalance

Option:

Function:

Operation under severe mains imbalance conditions reduces drive lift time.

Select function to take place when severe mains imbalance is detected.

[0]

*

Trip

Frequency converter trips.

[1]

Warning

Frequency converter issues a warning.

[2]

Disabled

No action taken.

4.11.4. Trip Reset, 14-2*

Parameters for configuring auto reset handling, special trip handling and control card self test or initialisation.

14-20 Reset Mode

Option:

Function:

Select reset function after tripping. Once reset, frequency converter can be restarted.

[0]

*

Manual Reset

Perform reset via [reset]-button or digital inputs.

[1]

AutoReset 1

Performs one automatic reset after tripping.

[2]

AutoReset 2

Performs two automatic resets after tripping.

[3]

AutoReset 3

Performs three automatic resets after tripping.

[4]

AutoReset 4

Performs four automatic resets after tripping.

[5]

AutoReset 5

Performs five automatic resets after tripping.

AF-60 LP™ Micro Drive Programming Guide

54

4

Advertising