4.7. Parameter Group 6: Analogue In/Out

4.7.1. 6-** Analog In/Out

Parameter group for configuring analog inputs and outputs.

4.7.2. 6-0* Analog I/O Mode

Parameter group for setting up the analog I/O configuration.

6-00 Live Zero Timeout Time

Range:

Function:

The Live Zero function is used for monitoring the signal on an analog input. If the signal disappears, a Live Zero warning

is reported.

10 s [1 - 99 s]

Set delay time before Live Zero Timeout Function is applied (par. 6-01).

If the signal reappears during the set delay, timer will be reset.

When live zero is detected, the frequency converter freezes output frequency and starts Live Zero Timeout timer.

6-01 Live Zero Timeout Function

Option:

Function:

Function is activated if input signal is below 50% of value set in parameters 6-10, 6-12 or 6-22.

[0]

*

Off

Function is disabled.

[1]

Freeze output

Output frequency remains at value it had when live zero was detected.

[2]

Stop

Frequency converter decels down to 0 Hz. Remove live zero error condition before restarting frequency converter.

[3]

Jogging

Frequency converter accels to jog speed, see par. 3-41.

[4]

Max Speed

Frequency converter accels to Motor Speed High Limit, see par. 4-14.

[5]

Stop and Trip

Frequency converter decels down to 0 Hz and then trips. Remove live zero condition and activate reset before restarting

the frequency converter.

4.7.3. 6-1* Analog Input 1

Parameters for configuring scaling and limits for analog input 1 (terminal 53).

NB!

Micro switch 4 in position U:

Parameters 6-10 and 6-11 are active.

Micro switch in position I:

Parameters 6-12 and 6-13 are active.

See AF-60 LP

Micro Drive Quick Guide