Leakage Current

The earth leakage current from the frequency converter exceeds 3.5 mA. According to IEC 61800-5-1 a reinforced Protective Earth connection

must be ensured by means of a min. 10mm² Cu or an addtional PE wire - with the same cable cross section as the Mains wiring - must be

terminated separately.

Residual Current Device

This product can cause a DC current in the protective conductor. Where a residual current device (RCD) is used for extra protection, only an

RCD of Type B (time delayed) shall be used on the supply side of this product.

Protective earthing of the frequency converter and the use of RCDs must always follow national and local regulations.

Motor overload protection is possible by setting Parameter 1-90 Motor thermal protection to the value Electronic overload trip. For the North

American market: Electronic overload functions provide class 20 motor overload protection, in accordance with NEC.

Installation in high altitudes:

For altitudes above 2 km, please contact GE .

1.1.5. IT Mains

IT Mains

Installation on isolated mains source, i.e. IT mains.

Max. supply voltage allowed when connected to mains: 440 V.

As an option, GE offers line filters for improved harmonics performance.

1.1.6. Avoid unintended Start

While the frequency converter is connected to mains, the motor can be started/stopped using digital commands, bus commands, references or via the drive

Keypad.

Disconnect the frequency converter from mains whenever personal safety considerations make it necessary to avoid unintended start of any motors.

To avoid unintended start, always activate the [OFF] key before changing parameters.

1.1.7. Disposal Instruction

Equipment containing electrical components must not be disposed of together with domestic waste.

It must be separately collected with electrical and electronic waste according to local and currently valid legislation.

1.1.8. Before Commencing Repair Work

1.

Disconnect AF-60 LP

റ Micro Drive from mains (and external DC supply, if present.)

2.

Wait for 4 minutes for discharge of the DC-link.

3.

Disconnect DC bus terminals and brake terminals (if present)

4.

Remove motor cable

AF-60 LP™ Micro Drive Programming Guide

4

1