Af-60 lp™ micro drive programming guide, 14-4* energy savings – GE Industrial Solutions AF-60 LP Micro Drive User Manual

Page 56

Advertising
background image

[6]

AutoReset 6

Performs six automatic resets after tripping.

[7]

AutoReset 7

Performs seven automatic resets after tripping.

[8]

AutoReset 8

Performs eight automatic resets after tripping.

[9]

AutoReset 9

Performs nine automatic resets after tripping.

[10]

AutoReset 10

Performs ten automatic resets after tripping.

[11]

AutoReset 15

Performs fifteen automatic resets after tripping.

[12]

AutoReset 20

Performs twenty automatic resets after tripping.

[13]

Infinite auto reset

Performs an infinite number of automatic resets after tripping.

Motor may start without warning.

14-21 Automatic Restart Time

Range:

Function:

10 s

*

[0 - 600 s]

Enter time interval from trip to start of automatic reset function. This parameter is active when par. 14-20, Reset

Mode, is set to Automatic Reset [1] - [13].

14-22 Operation Mode

Option:

Function:

Use this parameter for specifying normal operation or to initialize all parameters, except par. 15-03, 15-04 and 15-05.

[0]

*

Normal Operation

Frequency converter runs normal operation.

[2]

Restore Factory Settings Resets all parameters to default settings, except for 15-03, 15-04 and 15-05. Frequency converter resets during next

power-up.

Par. 14-22 also reverts to default setting Normal Operation [0].

4.11.5. 14-4* Energy Savings

These parameters are for adjusting the energy savings level in both Variable Torque (VT) and Energy savings modes.

14-41 Energy savingsMinimum Magnetization

Range:

Function:

66%

*

[40 - 75%]

Enter the minimum allowable magnetization for energy savings. Selecting a low value reduces energy loss in the motor,

but may also reduce resistance to sudden load changes.

AF-60 LP™ Micro Drive Programming Guide

55