4.9.4. 8-30 Protocol

8-30 Protocol

Option:

Function:

Select the protocol to be used. Note that changing protocol will not be effective until after powering off the frequency

converter.

[0]

*

GE Drive Protocol

[2]

Modbus RTU

8-31 Address

Range:

Function:

Select the address for the bus.

1

*

[1 - 126]

Drive-bus range is 1-126.

Modbus range is 1-247.

8-32 Drive Port Baud Rate

Option:

Function:

Select baud rate for Drive Port.

NB!

Changing baud rate will be effective after responding to any ongoing bus-requests.

[0]

2400 Baud

[1]

4800 Baud

[2]

*

9600 Baud

[3]

19200 Baud

[4]

38400 Baud

8-33 Drive Port Parity

Option:

Function:

This parameter only affects Modbus as Drive bus always has even parity.

[0]

*

Even Parity (1 stopbit)

[1]

Odd parity

[2]

No Parity (1 stopbit)

Select this for Modbus RTU

[3]

No Parity (2 stopbit)

8-35 Minimum Response Delay

Range:

Function:

0.010 s

*

[0.001 - 0.500 s]

Specify minimum delay time between receiving a request and transmitting a response.

8-36 Max Response Delay

Range:

Function:

5.000 s

*

[0.010 - 10.00 s]

Specify maximum permissible delay time between transmitting a request and receiving a response. Exceeding this time

delay causes control word timeout.

4.9.5. 8-5* Digital/Bus

Parameters for configuring control word Digital/Bus merging.

NB!

Parameters are only active when par. 8-01, Control SIte, is set to Digital and control word [0].

AF-60 LP™ Micro Drive Programming Guide