Af-60 lp™ micro drive programming guide, 5-4* relays – GE Industrial Solutions AF-60 LP Micro Drive User Manual

Page 34

Advertising
background image

[26]

Precise stop inverse (on-

ly terminal 33)

Prolong the stop signal to give a precise stop independent of scan time. The function is available for terminal 33 only.

[27]

Start, precise stop (only

terminal 33)

As [26], but including Start.

[28]

Catch up

Select Catch up/Slow down to increase or reduce the resulting reference value by the percentage set in par. 3-12.

[29]

Slow down

Same as Catch up [28]

[32]

Pulse input (only termi-

nal 33)

Select Pulse input when using a pulse sequence as either reference or feedback. Scaling is done in par. group 5-5*.

[34]

Ramp bit 0

Logic 0 = Ramp1, see par. 3-4*.

Logic 1 = Ramp2, see par. 3-5*.

[60]

Counter A (up)

Input for counter A.

[61]

Counter A (down)

Input for counter A.

[62]

Reset counter A

Input for reset of counter A.

[63]

Counter B (up)

Input for counter B.

[64]

Counter B (down)

Input for counter B.

[65]

Reset counter B

Input for reset of counter B.

5-10 Terminal 18 Digital Input

Option:

Function:

[8]

*

Start

Select function from available digital input range.

See par. 5-1* for choices.

5-11 Terminal 19 Digital Input

Option:

Function:

[10]

*

Reversing

Select function from available digital input range.

See par. 5-1* for choices.

5-12 Terminal 27 Digital Input

Option:

Function:

[1]

*

Reset

Select function from available digital input range.

See par. 5-1* for choices.

5-13 Terminal 29 Digital Input

Option:

Function:

[14]

*

Jog

Select function from available digital input range.

See par. 5-1* for choices.

5-15 Terminal 33 Digital Input

Option:

Function:

[16]

*

Preset bit 0

Select function from available digital input range.

See par. 5-1* for choices.

4.6.3. 5-4* Relays

Parameter group for configuring timing and output functions for relays.

[0]

No Operation

Default for all digital and relay outputs.

[1]

Control Ready

Control board receives supply voltage.

[2]

Drive Ready

Frequency converter is ready for operation and applies supply signal on control board.

[3]

Drive Ready, Remote

Frequency converter is ready for operation in Auto mode.

[4]

Enable/No Warning

Frequency converter is ready for operation. No start or stop command is given. No warnings are present.

[5]

Drive Running

Motor is running.

[6]

Running/No Warning

Motor runs, and no warning are present.

AF-60 LP™ Micro Drive Programming Guide

33

4

Advertising