4.12. Parameter Group 15: Drive Information

4.12.1. 15-** Drive Information

Parameter group containing information on operating data, hardware configuration, software version, etc.

4.12.2. 15-0* Operating Data

Parameter group containing operating data e.g. Operating Hours, kWh counters, Power Ups, etc.

4.12.3. 15-00 Operating Time

15-00 Operating Time

Range:

Function:

0 days

*

[0 - 65535 days]

View running hours of frequency converter.

The value is saved at power off and cannot be reset.

15-01 Running Hours

Range:

Function:

0

*

[0 - 2147483647]

View running hours of motor.

The value is saved at power off and can be reset in par. 15-07, Reset Running Hours Counter.

15-02 kWh Counter

Range:

Function:

0 [0 - 65535]

View power consumption in kWh as a mean value over one hour.

Reset counter in par. 15-06, Reset kWh Counter.

15-03 Power Ups

Range:

Function:

0 [0 - 2147483647]

View number of times frequency converter has been powered up.

Counter cannot be reset.

15-04 Over Temps

Range:

Function:

0 [0 - 65535]

View number of times frequency converter has tripped due to over temperature.

Counter cannot be reset.

15-05 Over Volts

Range:

Function:

0

*

[0 - 65535]

View number of times frequency converter has tripped due to over voltage.

Counter cannot be reset.

15-06 Reset kWh Counter

Option:

Function:

[0]

*

Do Not Reset

Counter is not reset.

[1]

Reset Counter

Counter is reset.

15-07 Reset Running Hours Counter

Option:

Function:

[0]

*

Do Not Reset

Counter is not reset.

[1]

Reset Counter

Counter is reset.