Electronic Overload

Warning

If calculated upper limit of motor temperature range is exceeded, a warning occurs.

[4]

Electronic Overload Trip

If 90% of calculated upper limit of motor temperature range is exceeded, an alarm occurs and frequency converter

trips.

NB!

When the Electronic Overload function has been selected the drive will store the recorded temperature at power down and this temperature will resume at

power up regardless of the elapsed time. Changing par. 1-90 back to [0] No Protection will reset the recorded temperature.

1-93 Thermistor Resource

Option:

Function:

Select the thermistor input terminal.

[0]

*

None

No thermistor is connected.

[1]

Analog Input 53

Connect thermistor to analog input terminal 53.

NB!

Analog input 53 cannot be selected for other purposes when selected as thermistor resource.

[6]

Digital input 29

Connect thermistor to digital input terminal 29.

While this input functions as thermistor input, it will not respond to the function chosen in par. 5-13, Digital Input 29.

The value of par. 5-13 remains however unchanged in parameter database while function is inactive.

Input Digital/

Analog

Supply Voltage

Threshold Cut-out

Values

Digital

10 V

<800 ohm - >2.9k ohm

Analog

10 V

<800 ohm - >2.9k ohm

AF-60 LP™ Micro Drive Programming Guide

21