This block performs a bistable timer.

The timer is activated on the rising or on the falling edge of input g in the following way:

l

On the rising edge of input g, output o is checked. If output o is FALSE the following operations

are performed:

l

Reading the delay time from input t-up.

l

Zero setting of the internal variable act (output act).

l

Enable of the timer, internal variable

is set TRUE (output

l

After t-up milliseconds are elapsed, during which input g is always TRUE, timer outputs are
set in the following way:

l

output o is set TRUE

l

output

is set FALSE

l

ouput act keeps the last value reached (t-up value)

l

On the falling edge of input g, output o is checked. If output o is TRUE the following operations
are performed:

l

Reading the delay time from input

l

Zero setting of the internal variable act (output act).

l

Enable of the timer, internal variable

is set TRUE (output

l

After

milliseconds are elapsed, during which input g is always FALSE, timer outputs

are set in the following way:

l

output o is set FALSE

l

output

is set FALSE

l

ouput act keeps the last value reached (t-up value)

When the timer is active, output

is TRUE, output act indicates the number of cycles elapsed from start

operations.

When output

is FALSE, output act could not be significant.

Input t-up

input

are read only in the cycle where a variation is checked, at the rising or falling edge

of input g. Therefore, if input

or input

values change while the timer is enabled, output

is

TRUE, the new value is not considered. This value will be used from the next timer activation.

All times are expressed in milliseconds (ms). Therefore, if input

is set to 12, timer output o changes with

12 milliseconds delay and output act changes from 0 to 12.