A n a l o g - I n p u t
Description
It reads
the input (In), multiplies by scale (Scale), adds an offset (Offset) and filters it
with a low pass filter
with a time constant of
FilterTau
Input logical variables
None
Output logical variables
None
Input ports
N a m e
Executed
In
float
always
Scale
float
always
Offset
float
always
float
always
Function
Input
to be read
Scale factor [y/x] multiplied by In input
Offset [y] added to In input
Time constant
of the first order low pass
filter. It must be greater than the cycle time of the
control. If not. the filter will be disabled.
Output ports
name
o u t
type function
float
output [y]