Chapter 8 I/O Parameter

221

[72] Allowable time of exceeding torque allowing continuous pressing (Parameter No.89)

No.

Name

Symbol

Unit

Input Range

Default factory

setting

89

Allowable time of exceeding

torque allowing continuous

pressing

PSCT

sec

0 to 300

In accordance with

actuator

This is the parameter to limit the continuous pressing time when using RCS2-RA13R with the

pressing setting of 71% or more.

When the unit is used beyond this limit, Alarm Code 0C4 “continuous pressing capable torque

time over” will be generated to prevent the temperature rise on the motor due to the continuous

pressing operation. [Refer to 10.4.2 Specifications and Limitations in Pressing Operation of

RCS2-RA13R.]

Parameter No.89

Description

0

Do not judge

1 to 300sec

Allowable time of continuous pressing

(when pressing setting of 71% or more is used in

RCS2-RA13R)

[73] Fieldbus I/O format (Parameter No.90)

This parameter is exclusively used for the controller of field bus specification.

Check the relevant Instruction Manual of each field bus.

[74] Current limit value at stopping due to miss-pressing (Parameter No.91)

No.

Name

Symbol

Unit

Input Range

Default factory

setting

91 Current limit value at stopping

due to miss-pressing

FSTP

0: Current limit value

during movement

1: Current limit value

during pressing

0

This parameter defines the restricted current value at stopping due to miss-pressing.

This restricted current value locks the servo till the next moving command.

Parameter No.91

Description

0

Current limit value during movement

(2.8 to 4 times of rating value depending on actuator

characteristics)

1

Press-motion current-limiting value

[75] Use of loadcell (Parameter No.92)

No.

Name

Symbol

Unit

Input Range

Default factory

setting

92 Use of loadcell

FFRC

0: Not Applicable

1: Use

0

This parameter defines whether the loadcell (option) is used or not.

Set Value

Description

0

Does not use the loadcell (when standard

actuator)

1

Use the loadcell (For the actuator with the

loadcell)

[Refer to 3.2.7 Pressing Operation Using Force Sensor Operation Ready.]