4 impossible communication – IAI America SCON-CA User Manual

Page 254

Advertising
background image

Chapter 9

Troubleshooting

244

9.2.4 Impossible Communication

Situation

Possible cause

Check/Treatment

Not connectable with

host machine

Not connectable with

ROBONET

1) Communication rates do not match.

2) The machine number (station

number) is set to be duplicate with

that of another unit or out of the

range.

3) Parameter No.17 “Minimum delay

time for slave transmitter activation”

is set incorrectly.

4) Poor wiring or disconnection of

communication cable�

1) Set the communication rate to

match that of the host machine.

[Refer to the Instruction Manual

of the host unit.]

2) Correct the unit number (station

number) setting.

Machine numbers (station

numbers) vary depending on

communication modes. Refer to

the Instruction Manual of each

communication mode.

(Note 1)

3) If the host device is that other

than ROBONET and RS485 is

used, and the host is in the

response timeout error, adjust

Parameter No.17 to a smaller

value (2 as reference). In any

other cases, increase or

decrease the value at will to

change the send/receive timing.

(If the operation is performed

properly, the transmission cycle

of the host is too fast. Always

check the response of SCON

before next transmission.)

If the controller is connected to

ROBONET, set the value or

parameter No.17 to “2". (Refer

to the Instruction Manual of

ROBONET [separate volume].)

If the controller is connected to

each of field buses (other than

RS485), it is unnecessary to

take the value of parameter

No.17 into account.

4) Review the wiring again. Check

if termination resistances are

connected to network terminals

with correct values.

(Note 1) Refer to the following Instruction Manual for communications:

RS485························ Section 10.1

DeviceNet ·················· DeviceNet Instruction Manual (separate volume)

CC-Link ······················ CC-Link Instruction Manual (separate volume)

PROFIBUS················· PROFIBUS Instruction Manual (separate volume)

CompoNet·················· CompoNet Instruction Manual (separate volume)

MECHATROLINK······· MECHATROLINK Instruction Manual (separate volume)

EtherCAT ··················· EtherCAT Instruction Manual (separate volume)

EtherNet/IP ················ EtherNet/IP Instruction Manual (separate volume)

ROBONET ················· ROBONET Instruction Manual (separate volume)