3 wiring method, 1 wiring of power circuit – IAI America SCON-CA User Manual

Page 76

Advertising
background image

Chapter 2 Wiring

66

2.3

Wiring Method

2.3.1 Wiring of Power Circuit

Supply the appropriate power from the following considering the controller type.

Power Supply Type

Specifications

Reference

Motor Power Supply
Control Power Supply

100V Specification : 100 to 115V AC �10% 50/60Hz

200V Specification : 200 to 230V AC �10% 50/60Hz

I/O Power Supply

24V DC �10%

When the PIO is used

Brake Power Supply 24V DC �10% 1A

For brake equipped type

The figure below shows a sample wiring of the power circuit.

L1

L2

L1C

L2C

NC

PE

Circuit

Breaker

Ground Fault

Circuit

Interrupter

1) Noise

Filter

2) Clamp Filter

3) Surge Protector

SCON

100V AC

or

200V AC

P

W

R

-

B

K

+

+24V

0V

Brake Power Supply

Input Connector

AC Power Supply

Input Connector

PIO Connector

A. Control Power Supply

B. Motor Power Unit

24V DC

Power

Supply

Brake

Release Box

Caution : Attaching noise filter 1) is a mandatory thing to do. Not doing so may cause

error or unexpected operation to the controller because of noise.

Also, the peripheral devices may receive an influence of this controller noise.

Attach 2) and 3) if necessary considering the noise environment and the power

supply condition. It is recommended to attach them even though it is not

mandatory.

Load current of SCON-CA varies depending on the connected actuator, etc. Select the circuit

breaker that suits to the specification.

[Refer to 1.3]

Parts Name

Model

Supplier

Position to attach

NF2010A-UP

SOSHIN ELECTRIC

CO.,LTD

1) Noise Filter

MC1210

DENSEI-LAMBDA

Attach in range of

300mm or less from

controller

2) Clamp Filter

ZCAT3035-1330

TDK

Attach as close as

possible to controller

3)

Surge

Protector R • A • V-781BWZ-2A

Okaya ELECTRIC

CO.,LTD

Attach at the input

terminal of noise filter

Advertising