Chapter 1 Specifications Check

34

1.7 Noise Elimination and Mounting Method

(1) Noise Elimination Grounding (Frame Ground)



(2) Precautions regarding wiring method

1) Wire is to be twisted for the power supply.

2) Separate the signal and encoder lines from the power supply and power lines.

(3) Noise Sources and Elimination

Carry out noise elimination measures for electrical devices

on the same power path and in the same equipment. The

following are examples of measures to eliminate noise

sources.

1) AC solenoid valves, magnet switches and relays

[Measure] Install a Surge absorber parallel with the

coil.

2) DC solenoid valves, magnet switches and relays

[Measure] Mount the windings and diodes in parallel.

Select a diode built-in type for the DC relay

Controller

Do not share the ground wire with or

connect to other equipment. Ground

each controller.

Earth Terminal

Grounding resistance at 100��or less

Field wiring terminals shall be

marked with wire range (More

than AWG14), conductor

material (Cu), insulation

temperature rating (More than

60�C) and tightening torque

(1.0 ~ 1.2N•m).

Connect using FG connection

terminal on the main unit.

Controller

Other

equipment

Controller

Other

equipment

Other

equipment

0V

R

C

+24V

0V

+24V

Relay

coil

Relay coil

Surge absorber