Chapter 9

Troubleshooting

249

Alarm

Code

Alarm

Level

Alarm Name

Cause/Treatment

0A7

Operation

release

Command deceleration

error

Cause

: Because there is not enough deceleration distance

when the deceleration is changed to a lower setting

during the operation, the actuator exceeded the soft

limit when deceleration was made from the current

position with the deceleration after the change.

Soft limit

Deceleration starting position

not resulting in soft limit overshoot

If a command is issued here,

soft limit overshoot will occur.

The cause is that the timing to make the next

movement command when the speed was changed

during the operation was late.

Treatment : Make the timing earlier for the movement command

for the deceleration speed change.

0A8

Unsupported

motor/encoder types

Cause

: The motor connected to the controller is not

applicable or the type of the encoder that the motor

is connected is not applicable.

Treatment : Please contact us if the alarm is issued even with

the applicable actuator and the same problem

happens again even after rebooting the power.

0A9

Loadcell data error

Cause

: The data acquired from loadcell at power-on or

software reset is incorrect.

Treatment : 1) Effect of noise is suspected. Check if there is a

device radiating the noise and have a treatment

to prevent receiving the noise.

2) The loadcell may be faulty. If the error keeps

occurring even with the power reboot for several

times, it is considered the loadcell is

malfunctioned. Please contact IAI.

0B3

Spurious absolute error

Cause

: Home-return operation was not performed properly.

1) Work is interfering with peripheral equipment in

the middle of home return.

2) Encoder Error

Treatment : 1) Remove the interference.

2) Please contact IAI.

0B4

Cold start

Electric angling

mismatching

Cause

: This alarm indicates that the position deviation

counter has overflowed.

Treatment : The alarm occurs when the actuator cannot be

operated.

Confirm about the load conditions, that the work

does not interfere with any object nearby or the

brake has been released, etc.

If the error occurs even when the servo is ON, the

cable breakage or disconnection is considered.

Check the cable connection. Please contact IAI if

there is no failure in the cable and connector

connections.

0B5

Operation

release

Z-Phase position error

The position where the Z-phase is detected before the home

return operation, is out of the specified range.

Cause

: Encoder Error

Treatment : Please contact IAI.