10.2 Way to Set Multiple Controllers with 1 Teaching Tool

It is usually necessary to connect the teaching tool to the controllers one by one when making a

setup to multiple controllers with one unit of teaching tool. In this section, explains how to

perform the settings without connecting and disconnecting the plug.

• Requisite devices :

(1) SIO Converter (RCB-TU-SIO-A or RCB-TU-SIO-B)� : 1 unit

(2) Controller Link Cable (CB-RCB-CTL002)�

: Required by the number of controllers

Accessories 1) 4-way junction (Manufactured by AMP 5-1473574-4)

: 1 unit

2) e-CON Connector (Manufactured by AMP 4-1473574-4) : 1 unit

3) Terminal Resistance (220��with a e-CON connector)

: 1 unit

Instead of the e-CON cable attached to the controller link cable, a terminal block may be used.

In this configuration, disconnect the e-CON connector from the controller link cable.

10.2.1 Connecting Example

Shown below is an example of connection.

Teaching Pendant

To be prepared by customer.

Cable included in PC software

<RCB-CV-MW, CB-RCA-SIO□□□>

<CB-SEL-USB030, RCB-CV-USB, CB-RCA-SIO□□□>

PC Software

(Option)

RS232C-compatible <RCM-101-MW>

USB-compatible <RCM-101-USB>

SIO Converter (with Terminal Resistor)

<RCB-TU-SIO-A> Vertical

<RCB-TU-SIO-B> Horizontal

e-CON Connector (Manufactured by AMP 4-1473562-4 : Housing Color Green)
e-CON Connector (Manufactured by AMP 3-1473562-4 : Housing Color Orange)
Junction (Manufactured by AMP 5-1473574-4)

GN

GN

GN

Terminal Resistance

R = 220Ω

Controller Link Cable

<CB-RCB-CTL002>

Axis No. Setting : 0

Axis No. Setting : n-1

Axis No. Setting : 1

1st unit

nth unit

2nd unit