Analog inputs and analog outputs, Danger, Warning – Proface LT4300M - 5.7 Modular HMI + Control" User Manual

Page 107

Advertising
background image

LT-4201TM/4301TM Hardware Manual

107

Analog Inputs and Analog Outputs

Overview

The rear module is equipped with:

2 ch Thermocouple/Temperature Probes (16-bit)

2 ch analog inputs (13-bit)

2 ch analog outputs (12-bit)

Analog Features

There are different terminal connection points for each type of analog signal.
Since current and voltage requires different adjustment values, you also need to configure the
desired type of input or output signal:

-10...10 Vdc voltage signal (default).

0...10 Vdc voltage signal

0...20 mA current signal.

4...20 mA current signal.

The temperature measurement values are converted into numeric values that can be processed
by the controller. For temperature measurements, the temperature rear module returns the
measured value in 0.1

° C (0.18° F) steps.

The table shows the analog features:

DANGER

FIRE HAZARD
Use only the recommended wire sizes for I/O channels and power supplies.
Failure to follow these instructions will result in death or serious injury.

WARNING

UNINTENDED EQUIPMENT OPERATION
Do not exceed any of the rated values specified.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.

Number and
Type of
Channels

Digital
Resolution

Voltage/Current

2 ch inputs

13 bit

-10...10 Vdc (digital value -4096 to 4095)
0...10 Vdc (digital value 0 to 8192)
0...20 mA (digital value 0 to 8192)
4...20 mA (digital value 0 to 8192)

2 ch inputs

16 bit

RTD (Resistance Temperature Detector):
PT100/PT1000/NI100/NI1000
Thermocouple: J, K, R, B, S, T, E, N

2 ch outputs

12 bit

-10...10 Vdc (digital value -2048 to 2047)
0...10 Vdc (digital value 0 to 4095)
0...20 mA (digital value 0 to 4095)
4...20 mA (digital value 0 to 4095)