Proface LT4300M - 5.7 Modular HMI + Control" User Manual

Page 31

Advertising
background image

LT-4201TM/4301TM Hardware Manual

31

Electromagnetic Susceptibility

The LT system meets electromagnetic susceptibility specifications as indicated in the table:

Characteristic

Specification

Range

Electrostatic discharge

IEC/EN 61000-4-2

8 kV (air discharge)
6 kV (contact discharge)

Radiated radio frequency
electromagnetic fields

IEC/EN 61000-4-3

10 V/m (80 MHz...3 GHz)

Fast transients / Burst noise IEC/EN 61000-4-4

Power lines: 2 kV
Digital I/O: 1 kV
Relay outputs: 2 kV
Ethernet line: 1 kV
COM line: 1 kV
CAN line: 1 kV

Surge immunity

IEC/EN 61000-4-5

Power supply: CM: 1 kV; DM: 0.5 kV
Digital I/O: CM: 1 kV; DM: 0.5 kV
Shielded cable: 1 kV
CM = common drive
DM = differential drive

Conducted disturbances
induced by radio- frequency
fields

IEC/EN 61000-4-6

10 Veff (0.15...80 MHz)

Mains terminal disturbance
voltage

EN 55011 (IEC/CISPR11)

150...500 kHz, quasi peak 79 dBµV

500 kHz...30 MHz, quasi peak
73 dBµV

Electric field strength

EN 55011 (IEC/CISPR11)

30...230 MHz, quasi peak
10 m@40 dBµV/m

230 MHz...1 GHz, quasi peak
10 m@47 dBµV/m