Analog Inputs and Analog Outputs

Analog Input Characteristics

The table describes the characteristics of the analog inputs:

Characteristic

Voltage input

Current input

Number of maximum input channels

2

Input type

Single-ended

Input range

-10... 10 Vdc/0...10 Vdc

0...20 mA/4...20 mA

Input impedance

1 M

Ω or more

250 ± 0.11%

Ω

Sample duration time

10 ms per channel + 1 scan time

Total input system transfer time

20 ms + 1 scan time

Input tolerance

Maximum deviation
at 25

° C (77° F)

without
electromagnetic
disturbance

± 1% of the full scale

Maximum deviation

± 2.5% of the full scale

Digital resolution

13 bits

Temperature drift

± 0.06% of the full scale

Common mode characteristics

80 db

Cross talk

60 db

Non-linearity

± 0.4% of full scale

Input value of LSB

5 mV

10

μΑ

Maximum allowed overload (no
damages)

± 30 Vdc (less than
5 minutes)
± 15 Vdc (No damage)

± 30 mA dc

Protection type

Photo coupler between input and internal circuit

Cable

Type

Shielded

Length

Must be less than 3 m for IEC61131-2
conformance. Maximum transmission distance is
10 m.

Terminal blocks

Type: 3.5 mm (0.137 in.) pitch
Terminal blocks are removable

Isolation

External input: Photo coupler isolation
Between channels: Non-isolated