Output management, Notice – Proface LT4300M - 5.7 Modular HMI + Control" User Manual

Page 47

Advertising
background image

LT-4201TM/4301TM Hardware Manual

47

Output Management

Introduction

The LT Unit includes Standard outputs and fast outputs.
The following output functions are configurable on fast outputs:

PWM output

Pulse output

High-speed Counter (Synchronize Output)

Fast Output Management Availability

The information refers to all LT with fast outputs:

Short-circuit or Over-Current on Outputs

There are two groups for the output’s short circuit and over-current.
Group 1 (Fast Output) has a short-circuit protection circuit between the output and V-. Group 2
(Standard Output) does not have this circuit.
LT-4201TM (Modular Type DIO) and LT-4301TM (Modular Type DIO):

Group 1: 2 points Fast Outputs (Q0 to Q1)

Group 2: 10 points Standard Outputs (Q2 to Q11)

LT-4201TM (Modular Type Analog) and LT-4301TM (Modular Type Analog):

Group 1: 2 points Fast Outputs (Q0 to Q1)

Group 2: 6 points Standard Outputs (Q2 to Q7)

The table describes the errors:

For more information on protecting outputs, refer to your controller wiring diagram and to the
general wiring rules (see page 32).
The Standard outputs of this equipment do not have built-in reverse polarity protection. Incorrectly
connecting polarity can permanently damage the output circuits or otherwise result in unintended
operation of the equipment.

Output Terminal

Function

Q0

Pulse Output/CH 0, PWM Output/CH 0,
High-speed Counter (Synchronize Output)/CH 0

Q1

Pulse Output/CH 1, PWM Output/CH 1
High-speed Counter (Synchronize Output)/CH 1

If...

then...

you have a short-circuit at 0 V on Fast Output

Fast Output is stopped and error message is generated.
For more details, refer to the GP-Pro EX Reference
Manual.

you have a short-circuit at 24 V on Fast Output

the current crossing the Fast Output is too high

NOTICE

DAMAGE TO FAST OUTPUTS

Ensure the use of adequate protection against short-circuits on the power supply to the fast
outputs.

Do not connect positive voltage to any of the DC fast outputs terminals.

Failure to follow these instructions can result in equipment damage.