LT-4201TM/4301TM Hardware Manual

41

Common Grounding

If exclusive grounding is not possible, use a common grounding point. Use grounding resistance
of 10

Ω or less, wire thickness of 2.6 mm or more, or your country’s applicable standard for the

grounding point.
Precautions:

Do not use common grounding, since it can lead to accidents and machine breakdown.

If the equipment does not function properly when grounded, disconnect the ground wire from
the FG terminal.

Grounding Procedure

NOTE: FG and SG terminals are internally connected in the LT. When connecting an external
device to the LT using the SG terminal, be sure to check that no short-circuit loop is created when
you setup the system.

Step

Action

1

Check that the grounding resistance is less than 100

Ω.

(Grounding resistance of 100

Ω or less, wire thickness of 1.6 mm or more, or

your country’s applicable standard.)

2

Create the connection point as close to the unit as possible, and make the wire
as short as possible. When using a long grounding wire, replace the thin wire
with a thicker wire, and place it in a duct.