LT System General Implementation Rules

40

Protective Earth Ground (PE) Cable Shielding

The following shows the steps when using shield cables for grounding the LT power supply,
Standard I/O, High-speed I/O, Analog I/O, Temperature Input, Communication cable so on.

NOTE: The shielding must be clamped securely to the conductive backplane to ensure a good
contact.

Exclusive Grounding

Connect the frame ground (FG) terminal on the power plug to an exclusive ground. When
supplying power to the LT unit, be sure to separate the input, output and power lines, as shown:

Step

Description

1 Strip the shielding for a length of

15 mm (0.59 in.)

2 Use the metal grounding clamp(2)

to attach the cable to the
backplane plate (1) as close as
possible to the LT.