137

Temperature Input (Temperature Probes) Characteristics

The table describes the characteristics of the Temperature Input (Temperature Probes):

WARNING

UNINTENDED EQUIPMENT OPERATION
Do not exceed any of the rated values specified.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.

Input Characteristics

Input sensor type

Pt100/Pt1000/Ni100/Ni1000

Input temperature range

Pt100/Pt1000: -200...600

° C (-328...1112° F)

Ni100/Ni1000: -20...200

° C (-4...392° F)

Measuring current

Pt100/Ni100

1.12 mA ± 3.5%

Pt1000/Ni1000

0.242 µA ± 3.5%

Input impedance

Typically 10 M

Ω

Sample duration time

10 ms+1 cycle time

Wiring type

2-wire or 3-wire connection configured by software
for all inputs

Conversion mode

Sigma delta type

Input filter

Low pass

Resolution temperature value

0.1

° C (0.18

°

F)

Detection type

Open circuit (detection on each channel)

Input tolerance*

Maximum
deviation at 25

° C

(77

° F) without

electromagnetic
disturbance

± 5

° C (41° F)

Maximum
deviation at
25...50

° C

(77...122

° F)

Pt type: ± 5.6

° C (42.08° F)

Ni type: ± 5.2

° C (41.36° F)

Temperature drift

30 ppm/

° C

Digital resolution

16 bits

Rejection in
differential mode

50/60 Hz

Typically 60 dB

Common mode
rejection

Typically 80 dB

Isolation method

Photo coupler Isolation

Permitted input signal

±5 Vdc max.

Cable length

Pt100/Ni100

20

Ω or less

Pt1000/Ni1000

200

Ω or less

Terminal blocks

Type: 3.5 mm (0.137 in.) pitch
Terminal blocks are removable

Noise resistance - cable

Shielded cable is necessary

* Excluding errors caused by the wiring