Warning – Proface LT4300M - 5.7 Modular HMI + Control" User Manual

Page 139

Advertising
background image

LT-4201TM/4301TM Hardware Manual

139

Analog Output Characteristics

The table describes the characteristics of the analog outputs:

WARNING

UNINTENDED EQUIPMENT OPERATION
Do not exceed any of the rated values specified.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.

Characteristic

Voltage Output

Current Output

Maximum number of outputs

2

Output range

-10... 10 Vdc/0...10 Vdc

0...20 mA / 4...20 mA

Load impedance

2 k

Ω or more

300

Ω or less

Application load type

Resistive load

Settling time

10 ms

Total output system transfer time

10 ms + 1 scan time

Output tolerance

Maximum
deviation at
25

° C (77° F)

without
electromagnetic
disturbance

± 1% of the full scale

Maximum
deviation

± 2.5% of the full scale

Digital resolution

12 bits

Temperature drift

± 0.06% of the full scale

Output ripple

± 50 mV

Cross talk

60 db

Non-linearity

± 0.5% of the full scale

Output value of LSB

6 mV

12

μΑ

Protection type

Photo coupler between input and internal circuit

Output protection

Short circuit protection: Yes
Open circuit protection: Yes

Output behavior if input power supply
is less than the power failed threshold

Set to 0

Cable

Type

Shielded

Length

Must be less than 3 m for IEC61131-2
conformance. Maximum transmission distance is
10 m.

Terminal blocks

Type: 3.5 mm (0.137 in.) pitch
Terminal blocks are removable

Isolation

External input: Photo coupler isolation
Between channels: Non-isolated

Advertising