LT Installation

66

The panel face is not inclined more than 30

° when installing the unit in a slanted panel:

The power plug is positioned vertically when the unit is vertically installed.

The unit is at least 100 mm (3.94 in.) away from adjacent structures and other equipment for
easier maintenance, operation, and improved ventilation:

Step

Action

1

Place the unit on a clean and level surface with the display panel facing
downward.

2

The support thickness depends on the material:

Steel sheet: between 1.5 and 6 mm (0.059 in. and 0.236 in.)

Plastic: between 3 and 6 mm (0.118 in. and 0.236 in.)

If the thickness is between 1 and 1.5 mm (0.039 in. and 0.059 in.) for a steel
sheet support or between 1 mm and 3 mm (0.039 in. and 0.118 in.) for plastic,
use the spacer adaptor supplied in accessory kit PFXZGMAK1 (sold separately).