135

The table describes the characteristics of the Pulse Output/PWM Output/High-speed Counter
(Synchronize Output):

Characteristic

Value

Output type

Sink/Source

Rated voltage

24 Vdc

Power supply input range

19.2...28.8 Vdc

Power supply reverse protection

Yes

Pulse output/PWM output current

50 mA/point, 100 mA/common

Response time for original input

2 ms

Isolation resistance

Between fast
outputs and
internal logic

10 M

Ω or more

Between power
supply port and
protective earth
ground (PE) =
500 Vdc

10 M

Ω or more

Residual voltage

for I = 0, 1 A

1.5 Vdc or less

Delay

Off to on (50 mA load): 1.1 ms
On to off (50 mA load): 1.1 ms
NOTE: The delay is not including the cable delay.

Minimum load impedance

80

Ω

Maximum Pulse output frequency

50 KHz

Maximum PWM output frequency

65 kHz

Accuracy Pulse
Output/PWM Output

Frequency

Accuracy

Duty

10...100 Hz

0.1%

0...100%

101...1000 Hz

1%

1...99%

1.001...20 kHz

5%

5...95%

20.001...45 kHz

10%

10...90%

45.001...65 kHz

15%

15...85%

Duty rate range

1...99%

Cable

Type

Shielded, including 24 Vdc power supply

Length

Maximum 5 m (16 ft)

Terminal blocks

Type: 3.5 mm (0.137 in.) pitch
Terminal blocks are removable

NOTE: When using the acceleration/deceleration pulse output, there is a 1% maximum error for the
frequency.