12.11. VERIFICATION OF VOLTAGE DROP ON MAIN LINES

Measurement voltage drop as a result of current flow through a main line or a part of it can
be very important if it is necessary:

Verify the capability of an existing main line to supply a load

Dimension a new installation

Search for possible causes of troubles on devices, loads, etc.. connected to a main line


Purpose of the test
Measure the maximum percentage value of voltage drop between two points of a main
line

Parts of the system to be checked
The test includes two sequential impedance measurements in the initial point of main
power line (typically downstream to a protection device) and in the final point of the same
line.

Allowable values
The instruments compares the calculated value of

V% maximum voltage drop to the set

limit value (according to applicable guidelines) according to the following relationship:

100

*

*

%

I

NOM

1

2

NOM

MAX

V

V

Z

Z

where:

Z

2

= End point impedance of the main line being tested

Z

1

= Initial point impedance (Offset) of the main line being tested (Z

2

> Z

1

)

I

NOM

=

Nominal current of protection device of the main line being tested

V

NOM

=

Phase-Neutral or Phase-PE nominal voltage of the main line being tested


















12.12. MEASUREMENT OF EARTH RESISTANCE IN TN SYSTEMS